Flex-Core Current Transformers
APPLICATION: To be used with any 5 amp indicating or recording ammeter or amp or watt transducer. CONSTRUCTION: Directional silicon steel is used for the flexible core. Secondary windings are of copper. Unit is encapsulated in silicone rubber which protects against moisture, dirt, oil and corona. Remains flexible from - 45° to + 200° C. INSULATION LEVEL: 600VAC - can be used over insulated conductors on higher voltage circuits.
FREQUENCY: 50-400Hz
SAFETY FACTOR: A self-contained voltage clamping circuit prevents dangerous high voltage across the secondary windings in case of accidental opening of the output leads when the primary circuit is energized. This circuit will trigger within 10 microseconds when the secondary voltage rises to 40 volts or more, clamping the output to less than 1 volt.
SECONDARY LEADS: 12 feet long with spade connectors.
COLOR: Transformer (red) - leads (yellow)
FLEX-CORE, 6625 McVey Blvd., Columbus, OH 43235. Tel: 614-889-6152; Fax: 614-876-8538.