Product/Service

220 MIL 15 KV XLP AL URD Cable

Source: King Wire Inc.
Medium voltage UD-P suitable for Primary Underground Distribution System
King Wire Inc.h="480" border="1" cellspacing="0" cellpadding="0" bordercolorlight="#FFFFFF" bordercolordark="#000000"> Part Number Description 2-01UD15UE000J 2 15KV UD-CU 220 EPR 16X14 JKT King Wire Inc.h="480" border="0" cellspacing="0" cellpadding="0">   King Wire Inc.h="480" border="1" cellspacing="0" cellpadding="0" bordercolorlight="#FFFFFF" bordercolordark="#000000"> Weights (lbs/1000ft) w/o Jacket w/ Embedded Jacket 756 825 King Wire Inc.h="480" border="0" cellspacing="0" cellpadding="0">   King Wire Inc.h="480" border="1" cellspacing="0" cellpadding="0" bordercolorlight="#FFFFFF" bordercolordark="#000000"> Conductor Concentric Neutral AWG Size Stranding No. of Wires AWG Size 2 7 16 14 King Wire Inc.h="480" border="0" cellspacing="0" cellpadding="0">   King Wire Inc.h="480" border="1" cellspacing="0" cellpadding="0" bordercolorlight="#FFFFFF" bordercolordark="#000000"> Diameters (inches) Conductor Over
Insulation
Over
Insl Shield
Over
Neutral Wires
Over
Embedded Jacket
.290 .780 ±.030" .840 ±.050" .970 1.075 King Wire Inc.h="480" border="0" cellspacing="0" cellpadding="0">   King Wire Inc.h="480" border="1" cellspacing="0" cellpadding="0" bordercolorlight="#FFFFFF" bordercolordark="#000000"> Ampacity 1/C Direct Buried 1/C Duct Buried 1/C Duct In Air 225 160 140 King Wire Inc.h="480" border="0" cellspacing="0" cellpadding="0">   King Wire Inc.h="480" border="0" cellspacing="0" cellpadding="1"> Applications
Medium voltage UD-P suitable for Primary Underground Distribution System; buried directly or installed in underground ducts or conduits or exposed to sunlight for above ground application. To be used at 15,000 volts or less. Rated for continuous operation at 90°C conductor temperature.
 

Description

Conductor: Bare aluminum stranded class B conductor (compressed stranding). Strand Shield: Extruded semi-conducting strand shield. Insulation: Ethylene propylene rubber (EPR) insulation. Insulation Shield: Extruded semi-conducting insulation shield. Neutral Wires: Coated or uncoated copper concentric neutral wires. Embedded Jacket: Non-conducting linear low density PE (LLDPE) encapsulating jacket with extruded red stripes. Optional semi-conducting PE jacket. King Wire Inc.h="480" border="0" cellspacing="0" cellpadding="1">

 
Maximum Conductor Temperature

Normal Continuous 90°C Overload 130°C Short Circuit 250°C King Wire Inc.h="480" border="0" cellspacing="0" cellpadding="1">

 
Features

Simultaneous extrusion of strand shield, insulation and insulation shield (triple extrusion, dry curing process) combines to form a virtually perfect cable core eliminating unequal electrical stress.

EPR insulation offers low moisture absorption, good chemical resistance, low dielectric loss and high dielectric strength. EPR insulation has a proven superior life span.
 

Options
  • Cable In Duct (C-I-C)
  • Parallel
  • Triplex
  • Strand Filled
Specifications

ICEA S-68-516/NEMA W/C-8
AEIC CS 6
Made in accordance to REA U-I

King Wire Inc.h="480" border="0" cellspacing="0" cellpadding="0">